Honeywell CC-PAIN01 Non-HART High Level Analog Input Module
Manufacturer: Honeywell Process Solutions
Model: CC-PAIN01 (P/N:51410069-175)
Series: Experion PKS C300 Series C I/O System
Type: 16-Channel Non-HART High Level Analog Input IOM
Function: Collect 4–20mA / 1–5V analog signals from conventional non-smart transmitters; convert analog field values to digital data for C300 controller process calculation; no HART digital communication function
1. Overview
CC-PAIN01 is the non-HART counterpart of CC-PAIH01 for Honeywell Experion PKS C300 DCS. It provides 16 configurable analog input channels (12 single-ended / 4 differential) for standard 4–20mA two-wire transmitters without HART protocol. It accurately acquires pressure, flow, temperature and level signals, converts analog measurements to high-precision digital signals for control logic operation. Compatible with CC-TAIX01 non-redundant and CC-TAIX11 redundant IOTA terminal bases, it supports hot-swap online replacement and G3 conformal coating, ideal for general process monitoring loops without smart HART instruments in power, petrochemical and water treatment industries.
2. Technical Specifications
• Power Supply: 24 VDC ±10%, typical power consumption 2.0W
• Channel Configuration: 12 single-ended / 4 differential, total 16 channels
• Supported Signals: 4–20mA, 1–5VDC, 0–5VDC
• HART Support: None, pure analog signal acquisition only
• ADC Resolution: 16-bit high precision analog-to-digital conversion
• Measurement Accuracy: ±0.08% FS at 25°C, ±0.18% FS full temperature range
• Channel Isolation: 1500V channel-to-system galvanic isolation, EMI suppression circuit
• Onboard Diagnostics: Wire break, over-range, short-circuit fault detection with LED indication
• Operating Temperature: -40°C ~ +70°C
• Storage Temperature: -40°C ~ +85°C
• Humidity: 5%~95% RH non-condensing
• Dimensions: 142 mm × 82 mm × 54 mm
• Weight: Approx. 0.35 kg
• Coating: G3 conformal coating for corrosive, humid plant environments
• Feature: Hot-swappable, compatible with simplex/redundant C300 controller architecture
• Certifications: CE, UL, CSA, Class 1 Div 2 hazardous area certified
3. Key Features
• 16 High-Density Non-HART Analog Inputs: Cost-effective solution for conventional non-smart transmitters without HART calibration demands
• Mixed Single-Ended/Differential Wiring: Differential mode eliminates ground loop interference for long field cables
• Full Channel Self-Diagnosis: Real-time fault alarm for open wire, short circuit and signal over-limit
• High Noise Immunity: High CMRR filtering and channel isolation resist industrial electromagnetic interference
• Hot-Swap Maintenance Design: Replace module online without shutting down C300 controller or disconnecting field wiring
• G3 Conformal Coating Protection: Resist dust, moisture and corrosive gas in control cabinets
• Redundant System Compatibility: Matches redundant IOTA bases for high-availability measurement loops
4. Applications
• Thermal & Combined Cycle Power Plant conventional pressure/temperature/flow signal acquisition
• Refinery & Petrochemical plant monitoring with non-HART analog transmitters
• Oil & Gas pipeline and compressor station general process variable measurement
• Water treatment, metallurgy and pharmaceutical continuous process monitoring
Honeywell © CC-PAIN01 Non-HART High Level Analog Input Module